How Is Stair Pressurization Designed for Safe Egress?
By Jeremy Mills, CEO & Founder, Apex Grid Engineering — USAF Veteran. · Updated 2026-09-15
Stair pressurization holds the exit stair at higher pressure than the fire floor with a fan sized for open doors, pressure relief for closed doors, and multiple injection points so every floor stays in the design pressure band.
I'm Jeremy Mills, CEO & Founder of Apex Grid Engineering and a U.S. Air Force veteran. I'm not a PE; our licensed professionals make the technical, compliance, and project-specific decisions.
Sizing for the open-door condition
I size the supply fan from the open-door case: the design number of open doors times the airflow needed through each to maintain outward velocity, plus the closed-door leakage of the rest of the stair, plus a margin for construction leakage that is always worse than the tables assume. The number of doors assumed open comes from the adopted standard and the AHJ's expectations — it represents a realistic evacuation, not every door in the building. Duct and shaft losses are calculated, not guessed, because the fan has to deliver the design flow at the farthest injection point. Then I run the closed-door case against the same fan: with relief devices modeled, the pressure must stay below the door-force limit at every floor, in both summer and winter stack conditions.
Controls, relief, and integration
The control sequence is what makes the two conditions coexist. On alarm, the pressurization fan starts, the relief damper or VFD modulates on stair pressure, and the system proves operation back to the fire alarm panel. I interlock the design with the building's HVAC so the air handlers serving the fire floor shut down or go to smoke mode instead of fighting the pressurization, and I coordinate with the smoke control sequence where the stair connects to pressurized lobbies or elevator shafts. Commissioning includes the pressure test the code requires: measured differentials with the design doors open and with all doors closed, plus door-force measurements at the worst-case floor. If the numbers do not land in the band, the fan speed, relief setpoints, or injection balancing get adjusted until they do.
Stair pressurization design checklist
A stair pressurization design is ready when it clears this checklist. The two failure modes — smoke entry and stuck doors — are both addressed here. • Fan sized for the design open-door condition plus leakage and construction margin • Automatic pressure relief (damper, VFD, or both) proven for the all-doors-closed condition • Multiple injection points on tall stairs for even pressure top to bottom, intake from clean air • Door opening forces verified below the code limit at maximum design pressure • Commissioning pressure tests with design doors open and all doors closed, integrated with the smoke control sequence
Which related engineering resources can help?
What else do project teams ask?
What pressure differential should a pressurized stair maintain?
Why does the design consider both open and closed doors?
Where should the pressurization fan inject air into the stair?