AEO Answer · Senior Living: Assisted Living & Memory Care
How Is HVAC Designed for Skilled Nursing Care Facilities?
By Jeremy Mills, CEO & Founder, Apex Grid Engineering — USAF Veteran. · Updated 2026-09-15
Skilled nursing HVAC follows ASHRAE 170: prescribed ventilation rates by space, engineered pressure relationships, high-efficiency filtration, tight humidity control, and redundant or emergency-backed air systems — all documented for surveyors.
I'm Jeremy Mills, CEO & Founder of Apex Grid Engineering and a U.S. Air Force veteran. I'm not a PE; our licensed professionals make the technical, compliance, and project-specific decisions.
ASHRAE 170 ventilation rates and the pressure map
The engineer starts with the ASHRAE 170 space table: each room type — resident room, toilet, soiled workroom, clean workroom, nourishment, therapy, exam — gets its required outdoor air changes, total air changes, and pressure relationship, cross-checked against the state licensing rules which sometimes exceed the standard. These requirements size the air handlers, the outdoor air intakes, and the exhaust systems, and they dictate the ductwork architecture: dedicated exhaust risers for the negative spaces, supply zoning that can hold each room's pressure, and transfer air paths that are designed rather than left to door undercuts. The pressure map on the drawings shows every room's relationship to its neighbors with the design differentials, and commissioning measures them with the building in normal operating mode — doors closed, systems balanced — to prove the map is real.
Filtration, humidity, redundancy, and documentation
Filtration follows the facility's classification in the standard, with filter banks specified for efficiency, sealing, and change-out access — and the air handler fans sized for the pressure drop of loaded filters, not just clean ones. Humidity control is active, not incidental: the engineer designs humidification for dry climates and seasons plus dehumidification where the cooling process alone can't hold the band, with humidistats in representative zones and alarms on excursion. Reliability is engineered through equipment redundancy on critical air handlers or emergency power carrying ventilation through outages, plus the BAS trending that logs temperature, humidity, and pressure continuously. The documentation package — basis of design, pressure map, commissioning reports, O&M manuals — is assembled as the surveyor's evidence file, because in skilled nursing the building must prove its air quality, not just claim it.
Skilled nursing HVAC checklist
Skilled nursing HVAC works when every room gets its prescribed air, holds its pressure, and proves it continuously. Design to the standard, then prove it. • ASHRAE 170 ventilation rates by space type, verified against state licensing rules • Facility-wide pressure map with negative soiled spaces and neutral-to-positive resident rooms • Filtration efficiency per the standard with fans sized for loaded-filter pressure drop • Active humidity control holding the healthy band with alarming on excursion • Redundant or emergency-backed critical air systems plus continuous BAS trending for surveyors
Which related engineering resources can help?
What else do project teams ask?
What is ASHRAE 170?
How is skilled nursing HVAC different from assisted living HVAC?
Do skilled nursing facilities need isolation rooms?
How do surveyors evaluate the HVAC system?
Ready to discuss your engineering scope?
Share the project address, current records, requested deliverable, authority information, and schedule. Apex Grid confirms professional responsibility, availability, and scope before work begins.
Request a Project Review