How Are Air and Waterside Economizers Designed for Data Centers?

By Jeremy Mills, CEO & Founder, Apex Grid Engineering — USAF Veteran. · Updated 2026-09-15

Airside economizers are designed with intake/exhaust louvers, filtration, and mixing dampers plus humidity control; waterside economizers with plate heat exchangers, tower/dry-cooler capacity, and chiller-bypass piping. Both need control sequences for changeover, integrated partial operation, and edge-case protection — designed and commissioned as a primary operating mode.

I'm Jeremy Mills, CEO & Founder of Apex Grid Engineering and a U.S. Air Force veteran. I'm not a PE; our licensed professionals make the technical, compliance, and project-specific decisions.

Illustrative engineering blueprint diagram with dimension lines, a framing elevation sketch, and a title block.

The concise answer

Airside economizers are designed with intake/exhaust louvers, filtration, and mixing dampers plus humidity control; waterside economizers with plate heat exchangers, tower/dry-cooler capacity, and chiller-bypass piping. Both need control sequences for changeover, integrated partial operation, and edge-case protection — designed and commissioned as a primary operating mode. The design discipline that separates good economizer projects from disappointing ones is treating the economizer as the plant's normal state rather than a bonus mode. In a favorable climate, the plant will spend most of its hours in some degree of economizer operation. Designing the sequences, setpoints, and maintenance access for a system that's 'rarely used' guarantees it will perform like one.

Airside versus waterside: the design details

Airside design is an air-handling engineering exercise at large scale: louver sizing for the full economizer airflow with acceptable pressure drop and rain and snow management, filtration banks selected for the site's air quality with pressure-drop monitoring and maintenance access, and damper sections — intake, exhaust, and recirculation — with actuators and controls capable of precise mixed-air control. Humidification or dehumidification capacity covers the moisture swings of outdoor air. Waterside design is a hydronic exercise: plate-and-frame heat exchangers selected for the approach temperatures the free cooling hours require, cooling tower or dry-cooler capacity that can produce the needed water temperatures in cold weather (including freeze protection for the tower), and piping with the valving to run the loop through the exchangers, around the chillers, or in integrated configurations. Strainers and water treatment protect the exchangers, because a fouled economizer heat exchanger quietly erases the savings.

Economizer design checklist

Economizers repay careful design many times over in energy savings. Here's what I make sure is covered. Design the mode you'll live in.

  • Equipment selected for the actual climate and air quality — filtration, freeze protection, and capacity matched to the site
  • Control sequences for changeover, integrated partial operation, and edge cases, written as primary operating logic
  • Humidity control strategy for airside systems: the moisture consequences of outdoor air, designed not discovered
  • Heat exchanger protection waterside: strainers, treatment, and maintenance access so performance doesn't degrade silently
  • Commissioning across the operating range with trend-data verification that economizer hours match the design prediction

What else do project teams ask?

What's the difference between an economizer and free cooling?
Free cooling is the objective — cooling without compressors. The economizer is the equipment and system that achieves it. 'Free cooling design' covers the strategy, climate analysis, and economics; 'economizer design' covers the dampers, heat exchangers, piping, and controls that actually do the work. The companion page addresses the strategy; this one addresses the hardware and sequences.
How do you prevent contamination with airside economizers?
Through filtration designed for the outdoor air quality at the site — typically high-efficiency filtration beyond standard commercial levels — plus pressurization control and intake placement away from contamination sources like loading docks, cooling tower drift, and vehicle exhaust. In areas with poor outdoor air quality, from wildfire smoke to industrial pollution, the design may limit airside economizer use or default to waterside.
What is integrated economizer operation?
It's the operating mode where the economizer and mechanical cooling work together: the economizer handles part of the load and the chillers trim the rest, rather than a hard switch between 'free' and 'mechanical.' Integrated operation captures savings across far more hours than changeover-only designs, but it needs more sophisticated controls and equipment that can modulate together — it's a design choice with real energy consequences.
How are economizer controls commissioned?
By proving the sequences across the operating range: changeover points verified against actual outdoor conditions, integrated operation demonstrated at partial conditions, and failure modes tested — what happens when a damper fails, when sensors drift, when conditions change rapidly. Trend data from the building management system should confirm the plant actually operates in economizer mode for the hours the design predicted; if it doesn't, the sequences need tuning, not the expectations lowered.

Ready to discuss your engineering scope?

Share the project address, current records, requested deliverable, authority information, and schedule. Apex Grid confirms professional responsibility, availability, and scope before work begins.

Request a Project Review

Get a quote on your project

Reviewed and sealed by licensed PEs. “Solid engineering and clear communication from start to finish.” — Jason Mitchell, Principal Architect

Tell us what you need and where the project is — quotes back within 12–24 hours on qualifying scopes.