Which Backflow Preventer Does Your Building Actually Need?
By Jeremy Mills, CEO & Founder, Apex Grid Engineering — USAF Veteran. · Updated 2026-09-15
Backflow preventer selection follows the hazard: reduced-pressure-zone (RPZ) assemblies or air gaps for high-hazard connections, double-check valve assemblies for low-hazard connections, and atmospheric or pressure vacuum breakers at fixtures. The plumbing code sets the minimums, the water purveyor sets the service-entrance requirements, and every assembly must be tested annually by a certified tester.
I'm Jeremy Mills, CEO & Founder of Apex Grid Engineering and a U.S. Air Force veteran. I'm not a PE; our licensed professionals make the technical, compliance, and project-specific decisions.
The concise answer
Backflow preventer selection follows the hazard: reduced-pressure-zone (RPZ) assemblies or air gaps for high-hazard connections, double-check valve assemblies for low-hazard connections, and atmospheric or pressure vacuum breakers at fixtures. The plumbing code sets the minimums, the water purveyor sets the service-entrance requirements, and every assembly must be tested annually by a certified tester. An air gap — a physical separation between the water outlet and the flood rim of a fixture — is the simplest and most foolproof protection, and it's required where the hazard is severe, like chemical vats. Where an air gap isn't practical, the RPZ is the workhorse: two independently acting check valves with a hydraulically dependent relief valve between them. If either check leaks, the relief opens and dumps to drain rather than letting contaminated water pass. That relief discharge is why RPZs need a floor drain and can't go just anywhere.
The coordination details engineers miss
Pressure drop is the big one. A 2-inch RPZ can eat 10 to 15 psi at design flow, and that loss has to be in the pressure budget from the start — I've reviewed designs where the booster pump was sized without it and the top floor paid the price. Location matters too: RPZs discharge water when they trip, so they need drainage; they contain test cocks that a tester must reach annually, so they need clearance; and they're not allowed in pits that can flood unless specifically approved. The water purveyor conversation should happen during design, not at final inspection. Purveyors maintain their own cross-connection programs, and their requirements for the service-entrance assembly — device type, location, bypass arrangements — are effectively law for that project. Getting their sign-off on the submittal saves the most expensive kind of rework: the kind discovered after the walls are closed.
Getting backflow right the first time
Backflow protection is one of those code items that's invisible when it's right and catastrophic when it's wrong — either a contamination event or a failed final inspection. The path to getting it right is straightforward. This is what I verify on every project with cross-connection hazards.
- Match the device to the hazard level per the plumbing code — RPZ or air gap for high hazard
- Confirm the service-entrance assembly type and location with the water purveyor during design
- Include the assembly's pressure drop in the building pressure budget before sizing pumps
- Provide a drain for RPZ relief discharge, freeze protection, and tester access clearance
- Schedule annual testing with a certified tester and a reporting path to the purveyor
Which related engineering resources can help?
What else do project teams ask?
What is backflow and why does it matter?
What's the difference between an RPZ and a double-check assembly?
Where are backflow preventers required?
Do backflow preventers need maintenance?